LeCroy 1458 HV Mainframe Slow Controls Manual


I. Getting Started.

  1. Double click HV Control Icon on Desktop.
  2. Start Running HV Control Program by pressing arrow icon in upper left corner of screen.
  3. The program will prompt you to select a template file (HV_latest file is the file with the most recent values) to load desired values into mainframe. These files are located in the directory c:/Users/Tof/template files/HV control. This template file has a specific format to be shown later. (See section IV)
  4. The Program will load all the desired values from template into the mainframe automatically. (This will take ~10 mins.)
  5. Next, the program will read measured values from mainframe and write to database. There should be a message on screen just above the Controls saying "Retrieving Data from Mainframe". You will not be able to control mainframe when you see this message.


II. Controlling the Program.

 

A. Reading setting and measured values.

Click Read Out Boards x-y to display boards x-y in read out tables.

CH = channel. Range is 0-11.

Req V = Requested Voltage.

Meas V = Measured Voltage.

Meas I = Measured Current.

Status = On for Enabled/ Off for disabled.

Board = Slot number/ Board Number given on the rear of the mainframe. Range is 0-15.

 

B. Plotting specific channel over a maximum of 24 hours.

  1. Go to the History Plot section.
  2. Enter desired board number and channel number on that board.
  3. Click Plot Button.
  4. Program will plot the measured current in History Plot Current (white) and the requested voltage (blue) and measured voltage (white) in the History Plot Voltage for the desired channel.

 

All controls listed below are locked out when the program is retrieving data from the mainframe.

 

C. Turning HV on and off.

  1. To turn on HV click HV ON Button.
  2. To turn off HV click HV OFF Button.
  3. HV LED is Yellow when HV is on and is white when it is off.

 

D. Changing Voltages and Enabling or Disabling Channels.

  1. Go to the Controls section.
  2. Enter a desired Board/Slot where you want to make the change and click Enter- the Enter button will depress once the values are displayed on the screen.
  3. Change desired voltages and/or enable or disable channels on board.
  4. Once done, click Send To Mainframe. The program will send all values to mainframe on that board as seen. The button will read Sending to Mainframe until all values have been sent and then all measured values read back.

 

E. Writing Template to Local Disk.

  1. Go to the Controls section.
  2. Click on Write Template.
  3. Program will prompt you with a browser so you may choose the name of the template file you want to save. Note: Save file as a tab delimited text file.
  4. Once you figure out a proper name and clicked ok to save, the program will save all current requested voltages and enable channel settings to a text file. (See section IV on template files.)
  5. Write Template button will read Writing to Template until process is complete.

 

F. Loading Template File from Local Disk.

  1. Go to the Controls section.
  2. Click Read Template.
  3. Program will open a browser and you must choose the template you wish to use.
  4. The program will then write all the loaded values to the mainframe and then read back all values from the mainframe. This will take ~10 mins.
  5. The Read Template button will display Sending to Mainframe until process is complete.
  6. The program will update HV_latest with the newly loaded settings.


III. Warning System.

 

A. Status Display and Color Codes.

  1. The Status Display mocks the back of the mainframe as each column is a board and each row is a channel.
  2. Color Codes.

 

B. Warning Alarm, Warning Alarm Switch, and Causes for Alarm.

  1. The alarm is a flashing button displayed in a separate window with a constant beep.
  2. To turn off alarm press the button.
  3. Causes for Alarm.
    1. Hardware Voltage Limit Trip, which disables the channel, is caused when the voltage exceeds this limit. The limit is set on the back panel of each HV board. Also, when this trip occurs, a red LED on the back panel of the board will be flashing.
    2. Current Trip occurs when current exceeds a software limit, set at the start of the program. This limit can not be changed while the program is running and is detector specific. When trip occurs, the channel will be disabled.
    3. Out of Range Trip occurs when the measured voltage is ± 5V greater then the requested voltage. This limit can not be set during the running of the program. The channel is disabled when trip occurs.


IV. Template File, Latest Settings File, and Writing to Database.

 

A. Template File.

Date: 11/22/99 4:15:06 
Channel Req V Enabled 
0       755      1 
0.1     754      1 
0.2     792      1 
0.3     793      1 
And so on. 
For Enable: 1 is enabled and 0 is disabled.

 

B. Latest File

 

C. Database


V. Stopping HV Mainframe Slow Controls.

1. Click the Press to Stop Monitoring Mainframe button.

2. The program will cycle through one more read out from the mainframe, which might take up to ten minutes.

3. Then, the program will write all values and settings to the database and will update latest setting file one last time.